错误代码

型号

品牌

错误类型

错误原因

解决办法

1

MOVITRAC-31C

SEW

Overcurrent

Short circuit/earth fault at the output.Motor too large.Faulty

output stage.

Remove short-circuit.Connect smaller motor.If fault can still

not be reset,contact SEW service.

2

MOVITRAC-31C

SEW

DC link voltage

DC link voltage too high.

Increase deceleration ramps.

3

MOVITRAC-31C

SEW

Brake chopper

Regenerative power too highBraking resistor circuit

interruptedShort-circuit in the brakingresistor circuitBraking

resistance value too highFaulty brake chopper

Increase deceleration ramps.Check connecting leads of

thebraking resistor.Check technical data of thebraking

resistor.Exchange MOVITRAC® 31C

5

MOVITRAC-31C

SEW

Regenerativeoverload

With active regen. n monit. (P520/P522)and speed control

(P770):faulty encoder signalswrong number of pole pairs

(P324/P344)value of increments (P773) not correct

Check encoder.Check encoder connection.Set number of pole pairs

correctly.Set value of increments correctly.

4

MOVITRAC-31C

SEW

Cont. overload

´t utilization too high (> 125(%)).

Reduce load.

6

MOVITRAC-31C

SEW

Overtemperature

Thermal overload of the inverter.

Reduce load and / or ensure adequatecooling.

7

MOVITRAC-31C

SEW

Phase failure

With active mains volt. monitor.(P530)Phase missing at TL.

X1:1/2/3.

Check mains supply.

10

MOVITRAC-31C

SEW

Direction ofrotation

Only with active speed control (P770):Encoder tracks A/A and

B/B areswapped in pairs.Motor rotates in opposite direction.Regen.

overload (i.e. with sagging hoist)because of excessive load or

BOOSTsetting too low (P321/P341).

Check encoder connection.Exchanging two motor phases.Reduce

load or increase BOOST.

11

MOVITRAC-31C

SEW

Speeddetection

Only with active speed control (P770):Faulty encoder

connection.FEN31C/FPI31C option not installed.

Check encoder connection.Insert correct option(FEN31C or

FPI31C).

12

MOVITRAC-31C

SEW

Mot. overload

With active n monit. (P510/P512)and speed control (P770):faulty

encoder signalswrong number of pole pairs (P324/P344)value of

increments (P773) not correct

Check encoder.Check encoder connection.Set number of pole pairs

correctly.Set value of increments correctly.

13

MOVITRAC-31C

SEW

Startingconditions

With active hoist function (P710/P712):Current too low during

the premagnetizationphase:Motor rated power selected too smallin

relation to the inverter rated power.Cross-section of the motor

leads toosmall.

Check startup data and carryout new startup if necessary.Check

inverter-motor connection.Check cross-section of the motorleads and

increase if necessary.

14

MOVITRAC-31C

SEW

Output open

With active hoist function (P710/P712):Two or all output phases

interrupted.Motor rated power selected too smallin relation to the

inverter rated power.

Check inverter-motor connection.Check startup data and carryout

new startup if necessary.

17

MOVITRAC-31C

SEW

Stack overflow

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

18

MOVITRAC-31C

SEW

Stack underflow

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

19

MOVITRAC-31C

SEW

NMI trap

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

20

MOVITRAC-31C

SEW

Undefinedopcode

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

21

MOVITRAC-31C

SEW

Protected instr.

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

22

MOVITRAC-31C

SEW

Word op.access

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

23

MOVITRAC-31C

SEW

nstruct. access

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly,

24

MOVITRAC-31C

SEW

Ext. bus access

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

25

MOVITRAC-31C

SEW

EEPROM

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

26

MOVITRAC-31C

SEW

No connection

Inverter electronics faulty.Possible cause: EMC effect.

The notes for EMC compliant installationmust be observed.The

reset for error 25 consists ofseveral steps:1. Factory setting

(P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault

occurs repeatedly, contactSEW service.

27

MOVITRAC-31C

SEW

Ext. terminal

External fault signal has appeared at a programmableinput

Eliminate the cause of the fault. Reprogramthe terminal, if

necessary

28

MOVITRAC-31C

SEW

FaultINTERBUS

FFI31C and control mode (P841) = Fieldbus:Faulty monitoring

signal.

Check Fieldbus connection.

32

MOVITRAC-31C

SEW

Copying

Only when copying the parameters (P820):Break or interference

in PC or FBG31Cconnection.

Check connection between inverter andPC. Remove FBG31C keypad

and plugagain.

33

MOVITRAC-31C

SEW

Master-slave

Connection master-slave is interrupted.0V5 connection (RS-485)

missingMaster or slave defined incorrectlyin P880.

Check master-slave connection.0V5-establish connection

betweenmaster and slaveSet P880 correctly.

34

MOVITRAC-31C

SEW

Fieldbustimeout

No communication between master andslave within the specified

time of theresponse monitoring.

Check communication routine of themaster.Increase fieldbus

timeout time (P571)/deactivate monitoring.

35

MOVITRAC-31C

SEW

ConnectionEncoder-FRS

Encoder connection faulty.Power supply of the encoder

faulty.

Check encoder connection.Check power supply of the

encoder.

36

MOVITRAC-31C

SEW

ConnectionMaster-slave

Only with FRS and cable break master-slave(P557) = YES:Setpoint

connection of slave (TL. 98-101)is disrupted.Master Speed 0

® slave FRS CTRLis disrupted.Slave FRS CTRL input

not assigned.Master Speed 0 output not assigned.No master inverter

available.Encoder < 512 pulses per revolution used.

Check installation.Check programming of the binaryinputs and

binary outputs.Check if encoder type is correct.

37

MOVITRAC-31C

SEW

FRS RAM fault

Internal fault.

If fault occurs repeatedly, contactSEW service.

38

MOVITRAC-31C

SEW

FRS processdata fault

Fault on interface between inverter andFRS.

If fault occurs repeatedly, contactSEW service.

39

MOVITRAC-31C

SEW

FRS parameterdata fault

Invalid value for FRS parameters (P55_).

Check parameter settings.

41

MOVITRAC-31C

SEW

FRS lag fault

Polarity of the encoder not set correctly.Acceleration ramps

too short.P-gain of the positioningcontroller too smallSpeed

controller not set property.Value for lag error tolerance too

small

Change polarity of encoder.Increase ramps.Increase

P-gain.Select new parameters forspeed controller.Increase lag error

tolerance (P551).Check wiring of encoder, motor andmains

phases.Check if mechanical system is sluggishor whether drive hit

an obstacle.

43

MOVITRAC-31C

SEW

Faultbinary output

Load on TL. X3:61 > 150 mA.Load on the otherbinary outputs

> 50 mAShort circuit on binary output.Capacitive load on binary

output.

Check installation of the binary outputs.

sew 31系列服务器报警12,SEW变频器MOVITRAC-31C系列故障代码表相关推荐

  1. sew 31系列服务器报警12,SEW变频器MOVITRAC-31C系列故障代码详表

    故障代码 故障现象/类型 故障原因 解决对策 1 Overcurrent Short circuit/earth fault at the output. Motor too large. Fault ...

  2. sew 31系列服务器报警12,SEW品牌变频器的MOVITRAC-31C系列故障代码详表

    故障代码 故障代码故障现象/类型故障原因解决对策 1过电流短路故障时土/输出.汽车太大了.错误输出阶段.去除短路.小型马达连接.如果故障仍不能重置,接触缝的服务. 2直流环节电压直流环节电压过高.增长 ...

  3. 三凌服务器显示E7,三菱变频器E6、E7故障原因及解决方法?

    三菱变频器E6.E7故障原因及解决方法? E6.E7故障对于广大用户来说一定不陌生,这是一个比较常见的三菱变频器典型故障,当然损坏原因也是多方面的. (1)集成电路1302H02损坏.这是一块集成了驱 ...

  4. 戴尔灵越系列服务器是什么,戴尔灵越系列哪个好-2021戴尔灵越系列型号选购推荐...

    戴尔这个品牌相信很多小伙伴都是非常熟悉的,旗下的灵越系列也是非常热销的笔记本系列,那么灵越系列有哪些型号推荐呢?今天我们就来盘点一下2021值得选购的戴尔灵越系列笔记本,感兴趣的小伙伴快来一起看看吧! ...

  5. 联想 p系列服务器,联想发布2020款ThinkPad P系列移动工作站产品线

    ThinkPad P1 ThinkPad P1的设计初衷是将ThinkPad X1笔记本的高端型号进一步强化,使之可以成为移动工作站中,它的对应孪生兄弟是ThinkPad X1 Extreme,所以在 ...

  6. ibm x系列服务器操作手册,IBM_X系列服务器操作手册v1.0.doc

    IBM_X系列服务器操作手册v1.0 IBM X系列服务器操作手册 PAGE PAGE 1 IBM X系列服务器 操作手册 Ver. 1.0 蓝色快车 武汉二站 肖涵 2008/7/6 目 录 TOC ...

  7. 修改服务器cimc地址,UCSC系列服务器的CIMC设置.PDF

    UCSC系列服务器的CIMC设置.PDF UCS C系列服务器的CIMC设置 目录 简介 先决条件 要求 使用的组件 网络图 规则 背景信息 CIMC 入门 初始设置 KVM 功能 接线 启动 KVM ...

  8. 三菱mr系列服务器故障代码a6,三菱数控系统伺服故障和报警代码大全,超实用!...

    伺服故障和报警代码大全,超实用! 使用三菱交流伺服系统主要由三个系列:MR-ES.MR-J2S.MR-J3. 通常故障情况可由伺服驱动器上显示代码来初步判断,以下是几种常见的故障及其排查方法: 1.A ...

  9. HP Gen9系列 服务器健康监控灯报警,系统诊断无错

    HP Gen9系列 服务器健康监控灯报警,系统诊断无错 原服务器标机自带一个服务器电源,后加了一个电源,进F10诊断,监控灯亮琥珀色 解决过程:1.进行对调测试,PS1与PS2位电源进行位置对调,检测 ...

最新文章

  1. php 缓冲区,PHP的输出缓冲区
  2. PHP 实现无限分类
  3. MySQL必知必会教程:深入理解MySQL技术内幕
  4. 从DataSet导出Txt
  5. JSON.stringify()还可以这么用
  6. python 日期格式校验_python – 如何验证时间格式?
  7. python 二维强度图_荐 python数据分析matplotlib库使用之二维图形绘制
  8. 安全和隐私:您知道系统中潜藏着什么吗?
  9. 支付宝:提现免费再延3年,不设上限!
  10. eclipse java jsp_Javaweb学习笔记4 使用Eclipse快速开发JSP
  11. Android NDK开发(1)----- Java与C互相调用实例详解
  12. QSqlTableModel模型使用详解
  13. cruise软件模型,混动仿真模型,IMMD架构混联混动仿真模型,Cruise混动仿真模型,混联混动汽车动力性经济性仿真
  14. JS学习——贪吃蛇代码(简易版)
  15. 隆重推荐:公民税权手册
  16. 基于原语的千兆以太网RGMII接口设计
  17. matlab读取多张图片数据
  18. vivo Z1的USB调试模式在哪里,打开vivo Z1USB调试模式的经验
  19. Odoo12社区版分拣单处理时生成欠单流程
  20. ln软链接调试mininet

热门文章

  1. GigaScience:ASaiM基于Galaxy微生物组分析框架
  2. Python使用numpy包编写自定义函数计算均方误差(MSE、mean squared error)、评估回归模型和时间序列模型、解读MSE评估指标
  3. R语言构建xgboost模型:基于稀疏数据(dgCMatrix which is a sparse matrix)、稠密数据(dense matrix)、xgb.DMatrix数据聚合
  4. R语言gganimate包创建可视化gif动图:gganimate包创建动态线型图动画基于transition_time函数、使用geom_point函数显示动画移动的数据点、并保留线图中的全部数据点
  5. seaborn将图例放置在图像外部并使用move_legend函数将图例(legend)放置在图像的顶部、且单行展开显示
  6. MySQL数据库中默认事务隔离级别是?
  7. Python基于MASK信息抽取ROI子图并构建基于迁移学习(densenet)的图像分类器实战(原始影像和mask文件都是二维的情况)
  8. R语言使用ggpubr包的ggarrange函数组合多张结论图:使用ggpubr包将多个可视化结论嵌套起来输出(ggarrange组合ggarrange组合后的图像)
  9. R语言基于glmnet构建Logistic回归模型使用L1正则化并可视化系数及最佳lambda值
  10. 增强学习or强化学习概述